FLORIDA GEOLOGICAL SURVEY 2. May choose to explore only those geophysical anomalies nearest the structure, preferably near areas of greatest damage with adequate justification. 3. If no anomalies are detected or if the anomalies are distant from the damage identified during the initial site visit, locate the SPT tests in close proximity to the damaged portions of the structure. 4. If sinkhole loss related geophysical anomalies or known or suspected sinkholes are distant, a SPT boring can be placed between the feature and the house in order to determine if the house has been affected by the processes that may have caused the remote feature. ii. Ensure that all potential subsurface causes of the damage are adequately characterized. Adequate characterization will include enough testing to reasonably confirm any subsurface causes) of the damage. iii. Site and location specific drilling equipment (truck or trailer mounted models, hand augers, and tripod) should be used. The only rationale for not drilling where the cause of the damage is likely to be manifested should be human health and safety or inability to obtain legal access. These should be documented in the report. iv. Utility location procedures should be followed to ensure the safety of drilling crews and others on site as well as the structure. Where local or state requirements exist for utilization of the services of utility location providers, they will be utilized. (note that utility location services will usually only work on public right-of-way and not on private property) v. The boring materials recovered and their depths should be documented and described in the drilling log. It is recommended that these shallow soils be tested by a calibrated manual cone penetrometer in order to complete documentation of the relative strengths of materials encountered in the boreholes. vi. All test holes should be backfilled or grouted in general accordance with applicable procedures established by the county or water management districts in Florida. e. Cone penetration tests mechanical (CPT), electric CPT, piezocone (CPTU), seismic piezocone (SCPTU), resistivity piezocone (RCPTU) and horizontal stress cone (HSC). Location criteria same as for d. above.